Battery Model: SPRO-LFP3.2V300AH Battery Material: LiFePO4 Nominal Voltage: 3.2V [min2.5V-max3.65V] Nominal Capacity: 300AH
Product Description
■ Specification for LiFePO4 Battery
Battery Model: SPRO-LFP3.2V300AH
Battery Material: LiFePO4
Nominal Voltage: 3.2V [min2.5V-max3.65V]
Nominal Capacity: 300AH
■ Product Picture/Drawing
■ Specification
SUNPRO LiFePO4 Prismatic Battery Cell 3.2VDC 300AH |
|
Model Name |
SPRO-LFP72174204-300AH |
Casing material |
Aluminum shell |
Nominal Voltage (DC) |
3.2V |
Rated Capacity (AH) |
300AH |
Voltage range (DC) |
2.5V-3.65V |
Internal Resistance (mΩ) |
≤ 0.8mΩ |
Cut-off Voltage (DC) |
Charging: 3.65V |
Discharging: 2.5V |
|
Charging Current |
60A (Standard, 0.2C) |
Max Charge Current |
300A (1C) |
Const. Discharge Current |
300A (1C) |
Peak Discharge Current |
600A (2C) |
Dimension |
D72*W174*H204mm |
Net Weight |
5.55kg |
Working Temperature |
Charging: 0°C- 60°C |
Discharging: -20°C- 60°C |
|
Storage Temperature |
Around -20°C – 35°C |
During transportation |
Around 20°C |
DOD (Depth of Discharge) |
80% |
Life Cycle (@0.2C rate/25°C) |
4000-5000 times |
Accessories |
Copper Busbars/ M6 screws |
Warranty (from shipping date) |
36 months |
Applications/Used at |
Solar & Wind system/RVs/Marine/UPS/Power tools |
■ Note
Users should configure a suitable BMS for strictly monitoring, management and protection.
The reversal charging is forbidden. Correctly connect the battery cells with Positive Pole and Negative Pole, otherwise short circuit would happen due to wrong connection on +/- terminal then cause damage and safety problem.
No matter what kind of charging mode is, once the temperature of the cell is above the maximum charging temperature, charging should be stopped.
If the batteries kept unused for a long time, it should be charged and discharged at the standard model every 3 or 6 months. Store the batteries in the state of 20%-30% SOC
(Voltage scope: 3.275V~3.305V).
■ General Performance
Item |
Test Methods and Condition |
Criteria |
Room temperature storage |
After standard charging, the battery is stored in an environment of 25±2°C for 30 days, and the 0.2CA discharge capacity (maintaining capacity) is tested. |
Capacity retention ≥85% |
0.2CA cycle 3 times, test recovery capacity (maximum discharge capacity of 3 weeks cycle) |
Capacity recover ≥85% |
|
High temperature storage |
After standard charging, the battery is stored in a 60±2°C environment for 7 days, and the 0.2CA discharge capacity (maintaining capacity) is tested. |
Capacity retention ≥60% |
0.2CA cycle 3 times, test recovery capacity (maximum discharge capacity of 3 weeks cycle) |
Capacity recover ≥80% |
■ Mechanical Characteristics
Item |
Test Methods and Condition |
Criteria |
Constant heat and humidity performance |
After standard charging, place the battery in a constant temperature and humidity chamber with a relative humidity of 90% to 95% for 48 hours, and take out the battery at an ambient temperature of 25 ± 2 °C for 2 hours. If there is no obvious change in appearance. Then discharge to 2.50V at 1.0 CA |
Discharge capacity ≥80% |
Vibration |
After standard charging, the battery is mounted on a vibrating table, and experiments are carried out in three vertical directions of X, Y, and Z. The vibration frequency is varied at a speed of 1 Hz/min between 10 and 55 Hz, the displacement amplitude is 0.8 mm, and the reciprocating vibration is 90 min. |
No obvious damage, leakage, smoke or explosion of the battery, battery voltage ≥ 3.70V |
Drop Test |
After the battery vibration test is completed, the free drop test is performed under the following conditions: |
No obvious damage, leakage, smoke or explosion of the battery. |
■ Safe Characteristic
Item |
Test Methods and Condition |
Criteria |
Heavy impact |
The battery is placed on the impact table, and the 10kg weight is free to fall from the height of 1m, and the battery that has been fixed on the fixture (the surface with the largest battery area should be perpendicular to the table) |
The battery does not ignite or explode |
Thermal shock |
The battery was placed in a hot box and the temperature was raised to 130 ± 2 ° C at a rate of (5 ± 2 ° C) / min and held for 30 min. |
The battery does not ignite or explode |
High temperature test |
After standard charging, the battery is placed in an oven at 90 ° C for 4 hours, then the battery is discharged at a constant current of 0.2CA to 2.50V, and then cycled 3 times. |
Capacity recovery rate ≥75% |
Overcharge |
After standard charging, the battery with the thermocouple is placed in the fume hood. The battery and the sliding varistor are connected in series to the constant current and constant voltage source. The voltage is adjusted to 4.8V. The current is adjusted to 5.0CA through the sliding varistor, and then the battery is 5.0CA. Charging, monitoring battery temperature changes during the test, when the battery temperature dropped to about 10 ° C lower than the peak, the experiment was terminated. The current is not required to maintain 5.0CA during the test. |
The battery does not ignite or explode |
Short circuit |
Place the battery with the thermocouple in the fume hood, short-circuit its positive and negative poles (the total resistance of the line is not more than 100mΩ), monitor the battery temperature change during the test, and end the test when the battery temperature drops to about 10 °C lower than the peak value. . |
The battery does not ignite or explode |
※Above testing of safe characteristic must be with protective equipment.
■ CAUTIONS IN USE
To ensure proper use of the battery please read the manual carefully before using it. Handling
▪ Do not expose to, dispose of the battery in fire.
▪ Do not put the battery in a charger or equipment with wrong terminals connected.
▪ Avoid shorting the battery
▪ Avoid excessive physical shock or vibration.
▪ Do not disassemble or deform the battery.
▪ Do not immerse in water.
▪ Do not use the battery mixed with other different make, type, or model batteries.
▪ Keep out of the reach of children.
■ Charge and Discharge
▪ Battery must be charged in appropriate charger only.
▪ Never use a modified or damaged charger.
▪ Do not leave battery in charger over 24 hours.
■ Storage
▪ Store the battery in a cool, dry and well-ventilated area.
■ Disposal
▪ Regulations vary for different countries. Dispose of in accordance with local regulations.
■ Battery operation instruction
▪ 1. Charging
Charging current Cannot surpass the biggest charging current which in this specification book stipulated。
Charging voltage Does not have to surpass the highest voltage range which in this specification book stipulated。
Charge temperature The battery must carry on the charge in the ambient temperature scope which this specification book stipulated。
Uses the constant electric current, and the constant voltage way charge, the prohibition reverse charges. Incorrect connection of the battery positive electrode and the negative terminal can damage the battery。
▪ 2. Discharging current
The discharging current does not have to surpass this specification book stipulation the biggest discharging current, the oversized electric current electric discharge can cause the battery capacity reduction and to cause the battery overheat。
▪ 3. Discharge temperature
The battery discharge must carry on in the ambient temperature scope which this specification book stipulated.
▪ 4. Over-discharges
After the short time excessively discharges charges immediately cannot affect the use, but the long time excessively discharges can cause the battery the performance, battery function losing. The battery long-term has not used, has the possibility to be able to be at because of its automatic flashover characteristic certain excessively discharges the condition, for prevented excessively discharges the occurrence, the battery should maintain the certain electric quantity。
▪ 5. Storing the Batteries
The battery should store in the product specification book stipulation temperature range. If has surpasses above for one months the long-time storage, suggested you should carry on additional charge to the battery.
■ Period of Warranty
The period of warranty is 2 year from the date of shipment. guarantees to give a replacement in case of cells with defects proven due to manufacturing process instead of the customers abuse and misuse.
■ Other The Chemical Reaction
Because batteries utilize a chemical reaction, battery performance will deteriorate over time even if stored for a long period of time without being used.
In addition, if the various usage conditions such as charge, discharge, ambient temperature, etc. are not maintained within the specified ranges the life expectancy of the battery may be shortened or the device in which the battery is used may be damaged by electrolyte leakage.
If the batteries cannot maintain a charge for long periods of time, even when they are charged correctly, this may indicate it is time to change the battery.
■ NOTICE
Before using the battery pack/packs, pls DO NOTE BELOW REMINDINGS:
# Battery appearance visual check: Once batteries received, pls check if the batteries with scratches or impacted. If yes, pls contact us at the first time.
# Use insulating plate between batteries for better isolation in case short circuit happens to cause battery damage.
# Do correctly connect the battery cells with Positive Pole and Negative Pole, otherwise short circuit would happen due to wrong connection on +/- terminal.
# DO NOT Power On the batteries before checking. Connect the batteries in series/parallel to a battery pack firstly. Do not Charge the battery pack at this step!
# Use the Multimeter to check the voltage of each battery cell, then connect the battery cells to 12V/24V/48V Battery Pack and then check the voltage of the whole battery pack.
# Connection Use Notice:
Do keep the battery cells at same voltage if you are going to connect them in series or parallel. If not, pls connect the battery cells in parallel (no charging at this step) to balance the voltage.
# Ensure the Voltage parameters and Correct Connection of the batteries normal, YOU CAN CHARGE/USE the Battery Pack.
# DO Recharge the Battery Packs every 3 months if they are shelved/not used for long time.
Email: sunpro@sunprobatteries.com
Mob.: +86 150 9990 8382
Tel.: +86 20 3113 6580
WeChat: +86 150 9990 8382
Skype: live:2514c96fdbc0765c
Whatsapp: +86 150 9990 8382
Sign In